Maintenance and Field Replacement
This section discusses the maintenanceand replacement procedures for selected devices.
Considerations
Tips and requirements for maintenance issues.
- All fans and power supplies are hot swappable.
- The switch can be running while a power supply is being installed or removed, but the power supply being replaced must not be connected to a power source.
- All slots must be filled or covered with a blank for operation (even though power supply or fans may not be functional).
- Before you begin, refer to the Arista Networks document Safety Information and Translated Safety Warnings available at: https://www.arista.com/en/support/product-documentation.
Note: Descriptions for the removal and replacement of power supplies and fans are for a representative power supply or fan. Locations of status indicator LEDs may differ. Refer to the front and rear panel illustrations of your device to locate the appropriate LED.
Power Supplies
The following steps are required when removing and replacing power supplies from a switch.
Note: Only a representative power supply module is shown in Figure 1. For the location of the power supply on your switch, refer to Rear Panel.
Removing a Power Supply
Installing a Power Supply
You must make space for installing the power supply by removing an existing one (Removing a Power Supply).
Fan Modules
Fan module requirements when hot swapping the modules.
Note: Hot swap fans within 30 seconds to prevent the switch from overheating. Ensure that the module you are replacing matches those already installed in the switch.
Removing a Fan Module
The following steps are required when removing or replacing fans from a switch.
Note: Only a representative fan module is shown in Figure 2. For the location of the fan modules on your switch, refer to Rear Panel.
Installing a Fan Module
You must make space for installing the fan module by removing an existing one (Figure 2).