Overview

Scope

This guide is intended for properly trained service personnel and technicians who need to install the following Arista Networks Data Center Switches:
  • DCS-7504N
  • DCS-7508N
  • DCS-7512N
  • DCS-7516N

 

Important:

Only qualified personnel should install, service, or replace this equipment.

 

Seul le personnel qualifié doit installer, service, ou remplacer cet équipement.

 

Receiving and Inspecting the Equipment

Upon receiving the switch, inspect the shipping boxes and record any external damage. Retain packing materials if you suspect that part of the shipment is damaged; the carrier may need to inspect them.

If the boxes were not damaged in transit, unpack them carefully. Ensure you do not discard any accessories packaged in the same box as the main unit.

Inspect the packing list and confirm that you received all listed items. Compare the packing list with your purchase of the 7500n series Modular Switches order. The Parts List provides a list of components included with the switch.

Installation Process

The following tasks are required to install and use the switch:

  1. Select and prepare the installation site (Site Selection).
  2. Assemble the installation tools listed (Tools and Parts Required for Installation).
  3. Attach the mounting brackets and install the switch in an equipment rack (7504N and 7508N Rack Mounting and 7512N and 7516N Shelf Rack Mount Installation).
  4. Connect the switch to the power source and network devices (Cabling the Power Supplies).
  5. Configure the switch (Configuring the Modular Switch).
     
    Important:

    Class 1 Laser Product: This product has provisions for installing Class 1 laser transceivers that provide optical coupling to the communication network. After a Class 1 laser product is installed, the equipment is a Class 1 Laser Product. The customer is responsible for selecting and installing the Class 1 laser transceiver and for ensuring that the Class 1 AEL (Allowable Emission Limit) per EN/IEC 60825, CSA E60825-1, and Code of Federal Regulations 21 CFR 1040 is not exceeded after the laser transceiver have been installed. Do not install laser products whose class rating is greater than 1. Refer to all safety instructions that accompany the transceiver before installation. Only Class 1 laser devices certified for use in the country of installation by the cognizant agency are to be utilized in this product.

     

    Produit Laser de classe 1: Ce produit a des dispositions pour installer des émetteurs-récepteurs de laser de classe 1 qui offre de couplage au réseau de communication optique.Une fois un produit laser de classe 1 est installé, l'équipement est un produit Laser de classe 1 (Appareil à Laser de Classe 1).Le client est responsable pour sélectionner et installer l'émetteur/récepteur de laser de classe 1 et pour assurer que la classe 1 AEL (limite d'émission admissible) par EN/IEC 60825, CSA E60825-1, et Code des règlements fédéraux 21 CFR 1040 ne soit pas dépassée après avoir installé l'émetteur/récepteur de laser. Ne pas installer des appareils à laser dont la cote de classe est supérieure à 1.Voir toutes les consignes de sécurité qui ont accompagné l'émetteur-récepteur avant l'installation. Seuls appareils laser de classe 1 certifiés pour une utilisation dans le pays d’installation par l’organisme compétent doivent être utilisées dans ce produit.

     

    Important:

    This product's ultimate disposal should be done per all national laws and regulations.

     

    L'élimination finale de ce produit doit être effectuée conformément à toutes les lois nationales etrèglements.

     

Obtaining Technical Assistance

Any customer, partner, reseller, or distributor holding a valid Arista Service Contract can obtain technical support in any of the following ways:

  • Email: このメールアドレスはスパムボットから保護されています。閲覧するにはJavaScriptを有効にする必要があります。. This is the easiest way to create a new service request.

    Include a detailed description of the problem and the “show tech-support” output.

     

  • Web: https://www.arista.com/en/support.

    You can create a support ticket through the support portal on our website. You may also download the most current software and documentation and view FAQs, Knowledge Base articles, Security Advisories, and Field Notices.

     

  • Phone:+1 866-476-0000 or +1 408-547-5502.

 

Important:

There are no user-serviceable parts inside. Refer all servicing to qualified service personnel.

 

Aucune pièce réparable par l'utilisateur à l'intérieur. Confiez toute réparation à un technicien qualifié.

 

Specifications

The Modular Switch Specifications table lists the specifications of Arista Data Center modular switches covered by this guide.

 

Table 1. Modular Switch Specifications
  DCS-7504N DCS-7508N DCS-7512N DCS-7516N
Height 7RU: 312 mm

(12.25 inches)

13RU: 578 mm

(22.75 inches)

18RU: 801 mm

(31.53 inches)

29RU: 1289 mm

(50.75 inches)

Width 483 mm

(19 inches) maximum

483 mm

(19 inches) maximum

483 mm

(19 inches) maximum

483 mm

(19 inches) maximum

Depth 795 mm

(31.3 inches)

795 mm

(31.3 inches)

849 mm

(33.4 inches)

941 mm

(37.1 inches)

Weight 101 kg

(222 lbs) fully loaded

400 lbs

(182 kg) fully loaded

300 kg

(661 lbs) fully loaded

465 kg

(1025 lbs) fully loaded

DC Input Voltage (per circuit) -48/-60 V DC -48/-60 V DC -48/-60 V DC -48/-60 V DC,
DC Branch Circuit Protection 100 A 100 A 100 A 100 A
AC Input Voltage (per circuit) 200-240 V 200-240 V 200-240 V 200-240 V
AC Branch Circuit Protection 20 A 20 A 20 A 20 A
Input Power Circuits 2 to 4 circuits 2 to 8 circuits 2 to 12 circuits 6 to 20 circuits
Ambient Temperature 0° to 40°C

(32° to 104°F)

0° to 40°C

(32° to 104°F)

0° to 40°C

(32° to 104°F)

0° to 40°C

(32° to 104°F)

Storage Temperature -40° to 70°C

(-40° to 158°F)

-40° to 70°C

(-40° to 158°F)

-40° to 70°C

(-40° to 158°F)

-40° to 70°C

(-40° to 158°F)

Relative Humidity 5 to 90% 5 to 90% 5 to 90% 5 to 90%
Altitude 0 to 3,000 meters

(0 to 10,000 feet)

0 to 3,000 meters

(0 to 10,000 feet)

0 to 3,000 meters

(0 to 10,000 feet)

0 to 3,000 meters

(0 to 10,000 feet)

Cooling See Power draw configurations in Table 2 See Power draw configurations in Table 2 See Power draw configurations in Table 2 See Power draw configurations in Table 2

 

The Table 2 table lists the power specifications of modular switch components.

 

Table 2. 7500n series Power Specifications
Module Type Part Number Power Draw (Typical / {Hot} Maximum)
Supervisor Modules DCS-7500E-SUP 47 W / 87 W
DCS-7500-SUP2 80 W / 120 W
DCS-7516-SUP 88 W / 130 W
linecard Modules DCS-7500E-36Q-LC 450 W / 556 W
DCS-7500E-72S-LC 212 W / 305 W
DCS-7500E-48S-LC 197 W / 285 W
DCS-7500E-12CM-LC 408 W / 495 W
DCS-7500E-6C2-LC 300 W / 320 W
DCS-7500E-12CQ-LC 414 W / 486 W
DCS-7500E-48T-LC 318 W / 332 W
DCS-7500R-36CQ-LC 758 W / 863W
DCS-7500R-36Q-LC 368 W / 406 W
DCS-7500R-48S2CQ-LC 202 W / 220 W
DCS-7500RM-36CQ-LC 944 W / 1040 W
DCS-7500R2-18CQ-LC 313 W / 350 W
DCS-7500R2-36CQ-LC 601 W / 654 W
DCS-7500R2A-36CQ-LC 830 W / 921 W
DCS-7500R2M-36CQ-LC 845 W / 941 W
DCS-7500R2AM-36CQ-LC 963 W / 1085 W
DCS-7500R2AK-36CQ-LC 830 W / 921 W
DCS-7500R2AK-48YCQ-LC 253 W / 276 W
DCS-7500R-8CFPX-LC 900 W / 1180 W
DCS-7500R3-36CQ-LC 410 W / 450 W
DCS-7500R3K-36CQ-LC 410 W / 450 W
DCS-7500R3-24P-LC 538 W / 558 W
DCS-7500R3-24D-LC 530 W / 550 W
Fabric Modules DCS-7504E-FM 80 W / 105 W
DCS-7508E-FM 155 W / 195 W
DCS-7504R-FM 121 W / 163 W / 237 W
DCS-7508R-FM 224 W / 298 W / 433 W
DCS-7512R-FM 570 W / 680 W / 760 W
DCS-7516R-FM 570 W / 770 W / 1053 W
DCS-7504R3-FM 220 W / 287 W
DCS-7508R3-FM 280 W / 387 W
Power Supply PWR-2700-DC-R (Fan Power) 43 W / 47 W
PWR-3KT-AC RED (Fan Power) 43 W / 47 W
PWR-3K-DC-RED (Fan Power) 43 W / 47 W
7504N series System Full chassis loaded with 2 DCS-7500E-SUP, 4 DCS-7504E-FM, 4 DCS-7500E-36Q-LC 3150 W / 3400 W
Full chassis loaded with 2 DCS-7500-SUP2, 4 DCS-7504R-FM, 4 DCS-7500E-36CQ-LC 3500 W / 4500 W
7508N series System Full chassis loaded with 2 DCS-7500E-SUP, 6 DCS-7508E-FM, 8 DCS-7500E-36Q-LC 5500 W / 6400 W
Full chassis loaded with:

2 - DCS-7500-SUP2

6 - DCS7508R-FM

8 - DCS-7500E-36Q-LC

5820 W / 6880 W / 7750 W
Full chassis loaded with:

2 - DCS-7500-SUP2

6 - DCS7508R-FM

8 - DCS-7500R-36CQ-LC

7720 W / 8990 W / 9880 W
Full Chassis loaded with:

2 - DCS-7500-SUP2

6 - DCS-7508R-FM

8 - DCS-7500R-36Q-LC

4600 W / 5360 W / 6230 W
Full Chassis loaded with:

2 - DCS-7500-SUP2

6 - DCS-7508R-FM

8 - DCS-7500R-48S2CQ-LC

3270 W / 3900 W / 4740 W
Full Chassis loaded with:

2 - DCS-7500-SUP2

6 - DCS-7508R-FM

8 - DCS-7500RM-36CQ-LC

9100 W / 10300 W / 11000 W
Full Chassis loaded with:

2 - DCS-7500-SUP2

6 - DCS-7508R-FM

8 - DCS-7500R2-36CQ-LC

6400 W / 7300 W/ 7900 W
7512N series System
Note: 7512N systems support only 7500R and 7500R3 series linecards.
Full chassis loaded with:

2 - DCS-7500-SUP2

6 - DCS75012R-FM

12 - DCS-7500R-36CQ-LC

12800 W / 14700 W / 15300 W
Full Chassis loaded with:

2 - DCS-7500-SUP2

6 - DCS-7512R-FM

9 - DCS-7500R-36CQ-LC

3 - DCS-7500R-36Q-LC

11600 W / 13300 W / 13900 W
Full Chassis loaded with:

2 - DCS-7500-SUP2

6 - DCS-7512R-FM

3 - DCS-7500R-36CQ-LC

9 - DCS-7500R-36Q-LC

9300 W / 10600 W / 11200 W
Full Chassis loaded with:

2 - DCS-7500-SUP2

6 - DCS-7512R-FM

12 - DCS-7500RM-36CQ-LC

14400 W / 16600 W / 18000 W*
Full Chassis loaded with:

2 - DCS-7500-SUP2

6 - DCS-7512R-FM

12 - DCS-7500R2-36CQ-LC

10200 W / 11800 W / 13200 W
7516N series System
Note: 7516N systems support only 7500R series linecards.
Full chassis loaded with:

2 - DCS-7516-SUP,

6 - DCS7516R-FM

16 - DCS-7500R-36CQ-LC

16 - PWR-3KT-AC-RED

16000 W / 19000 W / 21000 W
Full chassis loaded with:

2 - DCS-7516-SUP

6 - DCS7516R-FM

16 - DCS-7500R2-36CQ-LC

16 - PWR-3KT-AC-RED

13500 W / 15600 W / 17500 W
Full chassis loaded with:

2 - DCS-7516-SUP

6 - DCS7516R-FM

16 - DCS-7500RM-36CQ-LC

20 - PWR-3KT-AC-RED

19000 W / 22000 W / 24000 W

* Not N+N redundant power at worst case Temp/Elevation.

 

Note: Includes typical power supply conversion inefficiency. Contact your local Sales Engineer for 7500 power calculator details.

 

Note: Power numbers are given as Typical/Maximum or Typical/Hot/Maximum, where Hot is defined as 40°C Sea Level.