Overview
Scope
This guide is intended for properly trained service personnel and technicians who need to installArista Networks Data Center Switches.
This guide is intended for the following Arista Networks Data Center Switches:
DCS-7304 | DCS-7304X3 |
DCS-7308 | DCS-7308X3 |
DCS-7316 | |
DCS-7324 | |
DCS-7328 |
Seul le personnel qualifié doit installer, service, ou remplacer cet équipement.
Receiving and Inspecting the Equipment
Upon receiving the switch, inspect the shipping boxes and record any external damage. Retain packing materials if you suspect that part of the shipment is damaged; the carrier may need to inspect them.
If the boxes were not damaged in transit, unpack them carefully. Ensure that you do not discard any accessories that may be packaged in the same box as the main unit.
Inspect the packing list and confirm that you received all listed items. Compare the packing list with your purchase order. Parts List provides a list of components included with the switch.
Installation Process
The following tasks are required to install and use the switch:
- Select and prepare the installation site (Site Selection).
- Assemble the installation tools listed (Tools Required for Installation).
- Attach the mounting brackets and install the switch in an equipment rack (Two-Post Rack Mount).
- Connect the switch to the power source and network devices (Powering the Modular Switch and Connecting Serial and Management Cables).
- Configure the switch (Configuring the Switch).
Important: Class 1 Laser Product: This product has provisions to install Class 1 laser transceivers that provides optical coupling to the communication network. Once a Class 1 laser product is installed, the equipment is a Class 1 Laser Product (Appareil à Laser de Classe 1). The customer is responsible for selecting and installing the Class 1 laser transceiver and for insuring that the Class 1 AEL (Allowable Emission Limit) per EN/IEC 6-825, CSA E60825-1, and Code of Federal Regulations 21 CFR 1040 is not exceeded after the laser transceiver have been installed. Do not install laser products whose class rating is greater than 1. Refer to all safety instructions that accompanied the transceiver prior to installation. Only Class 1 laser devices certified for use in the country of installation by the cognizant agency are to be utilized in this product.
Produit Laser de classe 1: Ce produit a des dispositions pour installer des émetteurs-récepteurs de laser de classe 1 qui offre de couplage au réseau de communication optique.Une fois un produit laser de classe 1 est installé, l'équipement est un produit Laser de classe 1 (Appareil à Laser de Classe 1).Le client est responsable pour sélectionner et installer l'émetteur/récepteur de laser de classe 1 et pour assurer que la classe 1 AEL (limite d'émission admissible) par EN/IEC 60825, CSA E60825-1, et Code des règlements fédéraux 21 CFR 1040 ne soit pas dépassée après avoir installé l'émetteur/récepteur de laser. Ne pas installer des appareils à laser dont la cote de classe est supérieure à 1.Voir toutes les consignes de sécurité qui ont accompagné l'émetteur-récepteur avant l'installation. Seuls appareils laser de classe 1 certifiés pour une utilisation dans le pays d’installation par l’organisme compétent doivent être utilisées dans ce produit.
Important: Ultimate disposal of this product must be handled in accordance with all national laws and regulations.Aucune pièce réparable par l'utilisateur à l'intérieur. Confiez toute réparation à un technicien qualifié.
The fabric module requires special handling when removing, inserting, or handling the component. Fabric and Fan-only Module Description provides instructions for handing fabric modules.
Safety Information
Refer to the Arista Networks document Safety Information and Translated Safety Warnings available at: https://www.arista.com/en/support/product-documentation.
Obtaining Technical Assistance
Any customer, partner, reseller or distributor holding a valid Arista Service Contract can obtain technical support in any of the following ways:
- Email: http://This email address is being protected from spambots. You need JavaScript enabled to view it.. This is the easiest way to create a new service request.
Include a detailed description of the problem and the output of “show tech-support”.
- Web: https://www.arista.com/en/support.
A support case may be created through the support portal on our website. You may also download the most current software and documentation, as well as view FAQs, Knowledge Base articles, Security Advisories, and Field Notices.
-
Phone: +1 866-476-0000 or +1 408-547-5502.
Note:No user serviceable parts inside. Refer all servicing to qualified service personnel.
Aucune pièce réparable par l'utilisateur à l'intérieur. Confiez toute réparation à un technicien qualifié.
Specifications
Table 1 lists specifications of Arista Data Center modular switches and components covered by this guide.
DCS-7304/7324/7304X3 | DCS-7308/7328/7308X3 | DCS-7316 | |
---|---|---|---|
Height | 8 RU: 353mm (13.9 inches) | 13 RU: 572 mm (22.5 inches) | 21 RU: 930 mm (36.6 inches) |
Width | 442 mm (17.4 inches) | 442 mm (17.4 inches) | 442 mm (17.4 inches) |
Depth | 602 mm (23.7 inches) | 602 mm (23.7 inches) | 706 mm (27.8 inches) |
Weight | |||
Empty | 36 kg (78 lbs) | 50 kg (110 lbs) | 81 kg (178 lbs) |
Fully Loaded | 89 kg (196 lbs) | 140 kg (309 lbs) | 244 kg (536 lbs) |
Input Power (per circuit) | |||
AC Power | 200 - 240 VAC, 16 A (20 A US), 50 or 60 Hz | 200 - 240 VAC, 16 A (20 A US), 50 or 60 Hz | 200 - 240 VAC, 16 A (20 A US), 50 or 60 Hz |
DC Power | -48 - -60 VDC, 80 A | -48 - -60 VDC, 80 A | -48 - -60 VDC, 80 A |
Branch Circuit Protection | |||
AC Power | 20 A | 20 A | 20 A |
DC Power | 100 A | 100 A | 100 A |
Input Power Circuits | 1 to 4 circuits | 2 to 6 circuits | 3 to 8 circuits |
Operating Temperature | 0° to 40°C (32° to 104°F) | 0° to 40°C (32° to 104°F) | 0° to 40°C (32° to 104°F) |
Storage Temperature | -40° to 70°C (-40° to 158°F) | -40° to 70°C (-40° to 158°F) | -40° to 70°C (-40° to 158°F) |
Operating Altitude | 0 to 3,000 meters (0 to 10,000 feet) | 0 to 3,000 meters (0 to 10,000 feet) | 0 to 3,000 meters (0 to 10,000 feet) |
Relative Humidity | 5 to 90% | 5 to 90% | 5 to 90% |
Cooling | 6000 W maximum | 9000 W maximum | 12000 W maximum |
Table 2 lists power specifications of modular switch components.
Module Type | Part Number | Power Draw Typical / Maximum |
---|---|---|
Supervisor Modules | DCS-7300(-D)-SUP | 65 W / 80 W |
Linecard Modules | DCS-7300X-32Q-LC
DCS-7300X-64S-LC DCS-7300X-64T-LC DCS-7320X-32C-LC DCS-7300X3-32C-LC DCS-7300X3-48YC4-LC |
219 W / 372 W
166 W / 232 W 279 W / 430 W 428 W / 516 W 284 W / 491 W 193 W / 228 W |
Fabric Modules | DCS-7304X-FM
DCS-7308X-FM DCS-7316X-FM DCS-7324X-FM DCS-7328X-FM DCS-7304X3-FM DCS-7308X3-FM |
98 W / 172 W
195 W / 343 W 550 W / 760 W 192W / 288 W 380W / 578 W 98 W / 172 W 195 W / 343 W |
Fan-Only Modules | DCS-7304-S-FAN
DCS-7308-S-FAN |
16 W / 32 W
32 W / 64 W |
Power Supplies | PWR-2700-DC (fan power
PWR-3K-AC (fan power) PWR-3KT-AC (fan power) PWR-3K-DC (fan power) |
43 W/ 43 W
43 W/ 43 W 43 W/ 43 W 43 W/ 43 W |
7304 Series System | Full chassis loaded with four
DCS-7300X-64T-LC line cards |
1573 W / 3048 W |
7308 Series System | Full chassis loaded with eight
DCS-7300X-64T-LC line cards |
3077 W / 4972 W |
7316 Series System | Full chassis loaded with Sixteen
DCS-7300X-64T-LC line cards |
6729 W / 10080 W |
7324X Series System | Full chassis loaded with four
DCS-7320X-32C-LC line cards |
2545 W / 3376 W |
7328X Series System | Full chassis loaded with eight
DCS-7320X-32C-LC line cards |
5009 W / 6600 W |
7304X3 Series System | Full chassis loaded with four
DCS-7300X3-32C-LC line cards |
1885 W / 3078 W |
7308X3 Series System | Full chassis loaded with eight
DCS-7300X3-32C-LC line cards |
4005 W / 6490 W |
Table 3 lists 7300X Series switch components.
Chassis Model | Fabric Module | Fan-only Module |
Fan Spare |
Line Card | Power Supply |
---|---|---|---|---|---|
DCS-7304 (Forward) | DCS-7304X-FM-F | DCS-7304-S-FAN-F | FAN-7002-F | DCS-7300X- 32Q-LC
DCS-7300X- 64S-LC DCS-7300X- 64T-LC |
PWR-3K-AC-F
PWR-2700-DC-F |
DCS-7304 (Reverse) | DCS-7304X-FM-R | DCS-7304-S-FAN-R | FAN-7002-R | DCS-7300X- 32Q-LC
DCS-7300X- 64S-LC DCS-7300X- 64T-LC |
PWR-3K-AC-R
PWR-2700-DC-R |
DCS-7308 (Forward) | DCS-7308X-FM-F | DCS-7308-S-FAN-F | FAN-7002-F | DCS-7300X- 32Q-LC
DCS-7300X -64S-LC DCS-7300X- 64T-LC |
PWR-3K-AC-F
PWR-2700-DC-F |
DCS-7308 (Reverse) | DCS-7308X-FM-R | DCS-7308-S-FAN-R | FAN-7002-R | DCS-7300X- 32Q-LC
DCS-7300X- 64S-LC DCS-7300X- 64T-LC |
PWR-3K-AC-R
PWR-2700-DC-R |
DCS-7316 (Forward) | DCS-7316X-FM-F | Not Available | FAN-7002-F | DCS-7300X- 32Q-LC
DCS-7300X- 64S-LC DCS-7300X- 64T-LC |
PWR-3K-AC-F
PWR-2700-DC-F PWR-3K-AC-R PWR-2700-DC-R |
DCS-7316 (Reverse) | DCS-7316X-FM-R | Not Available | FAN-7002-R | DCS-7300X- 32Q-LC
DCS-7300X- 64S-LC DCS-7300X- 64T-LC |
PWR-3K-AC-F
PWR-2700-DC-F PWR-3K-AC-R PWR-2700-DC-R |
Table 4 lists 7320X Series switch components.
Chassis Model | Fabric Module | Fan Spare | Line Card | Power Supply |
---|---|---|---|---|
DCS-7324X (Forward) | DCS-7324X-FM-F | FAN-7002H-F | DCS-7320X-32C-LC | PWR-3KT-AC-BLUE |
DCS-7328X (Forward) | DCS-7328X-FM-F | FAN-7002H-F | DCS-7320X-32C-LC | PWR-3KT-AC-BLUE |
Table 5 lists 7300X3 Series switch components.
Chassis Model | Fabric Module | Fan Spare | Line Card | Power Supply |
---|---|---|---|---|
DCS-7304X3 | DCS-7304X3-FM | FAN-7002H-F | DCS-7300X3-32C-LC | PWR-3KT-AC-BLUE |
DCS-7308X3 | DCS-7308X3-FM | FAN-7002H-F | DCS-7320X-32C-LC | PWR-3KT-AC-BLUE |
Table 6 lists an AC and DC Power Supply Unit (PSU) comparison of circuit, cabling, and airflow for the DCS-7304, DCS-7308, and DCS-7316.
Model | Supported Chassis | Input Power (Per Circuit) | Branch Circuit Protection | Required Cabling and Interconnect | ||
---|---|---|---|---|---|---|
Description | Qty | PSU Air Flow | ||||
PWR-3K-AC-R
PWR-3K-AC-F |
DCS-7304
DCS-7308 DCS-7316 |
200 - 240 VAC
16 A (20 A US) 50 or 60 Hz |
20 A | Power cables: 14 AWG, C19-C20 | One for each AC power supply module supplied with switch. | Reverse (Red)
Forward (Blue) |
PWR-3KT-AC- BLUE | DCS-7304
DCS-7308 |
200 - 240 VAC
16 A (20 A US) 50 or 60 Hz |
20 A | Power cables: 14 AWG, C19-C20 | One for each AC power supply module supplied with switch. | Forward (Blue) |
PWR-2700-DC-R
PWR-2700-DC-F |
DCS-7304
DCS-7308 DCS-7316 |
-48 to -60 VDC
80 A |
100 A | DC Adapter (Arista part number CON-00581)
2 hole compression lug (not included) |
One DC adapter per power supply
2 compression lugs per DC Adapter |
Reverse (Red)
Forward (Blue) |
PWR-3K-DC- BLUE | DCS-7304
DCS-7308 |
-48 to -60 VDC
82.5 A |
100 A | 2 hole compression lug (not included) | 2 compression lugs per DC Adapter | Forward (Blue) |
Table 7 lists the power supply setup for LED status indicators.
Power Supply State | LED Name | PWR-3K-AC-Blue | PWR-3KT-AC-R | PWR-2700-DC-R | PWR-3K-DC-Blue |
---|---|---|---|---|---|
PWR-3K-AC-Red | PWR-3KT-AC -F | PWR-2700-DC-F | PWR-3K-DC-Red | ||
Input power present
Normal Operation |
Vin Good
DC Good Fault |
Green
Green Off |
Green
Green Off |
Green
Green Off |
Green |
Input power present
Main output off |
Vin Good
DC Good Fault |
Green
Off Off |
Green
Off Off |
Green
Off Off |
Blinking Green |
Input power present
Power Supply Fault |
Vin Good
DC Good Fault |
Green
Off Blinking Amber |
Green
Off Blinking Amber |
Green
Off Blinking Amber |
Blinking Amber, 1 sec on, 1 sec off |
No Input Power
Supply installed in chassis |
Vin Good
DC Good Fault |
Off
Off Off |
Off
Off Off |
Off
Off Off |
Off |
Input power present
Supply not seated in chassis |
Vin Good
DC Good Fault |
Off
Off Off |
Off
Off Blinking Green |
Off
Off Off |
Blinking Amber, 0.5 sec on/off |