Overview
This section discusses the following topics:
Scope
- DCS-7804
- DCS-7808
- DCS-7812
- DCS-7816
- DCS-7816L
Seul le personnel qualifié doit installer, service, ou remplacer cet équipement.
Receiving and Inspecting the Equipment
Upon receiving the switch, inspect the shipping boxes and record any external damage. If you suspect that part of the shipment is damaged, retain packing materials; the carrier may need to inspect them.
If the boxes were not damaged in transit, unpack them carefully. Do not discard any accessories that may have been packaged in the same box as the main unit.
Inspect the packing list and confirm that you received all listed items. Compare the packing list with your DCS-7800 Series Modular Switches purchase order. The Parts List provides a list of components included with the switch.
Installation Process
Perform the following steps to install and use the switch:
Safety Information
Refer to the Arista Networks document Safety Information and Translated Safety Warnings at https://www.arista.com/en/support/product-documentation.
Obtaining Technical Assistance
- Email: support@arista.com. Send an email to create a new service request.
Include a detailed description of the problem and the “show tech-support” output.
- Web: https://www.arista.com/en/support.
You can create a support case using the portal on our website. You can also download the most current software and documentation and view FAQs, Knowledge Base articles, Security Advisories, and Field Notices.
- Phone: +1 866-476-0000 or +1 408-547-5502.
There are no user-serviceable parts inside. Refer all servicing to qualified service personnel.
Aucune pièce réparable par l'utilisateur à l'intérieur. Confiez toute réparation à un technicien qualifié.
Specifications
The following table lists the specifications of Arista Data Center modular switches covered by this guide.
DCS-7804 | DCS-7808 | DCS-7812 | DCS-7816 | DCS-7816L | |
---|---|---|---|---|---|
Height | 10 RU: 439 mm
(17.28 inches) |
16 RU: 702 mm
(27.64 inches) |
23 RU: 1012 mm
(39.84 inches) |
32 RU: 1422 mm
(55.98 inches) |
32 RU: 1422 mm
(55.98 inches) |
Width | 441 mm
(17.36 inches) maximum |
441 mm
(17.36 inches) maximum |
441 mm
(17.36 inches) maximum |
441 mm
(17.36 inches) maximum |
441 mm
(17.36 inches) maximum |
Depth | 940 mm
(37.01 inches) |
940 mm
(37.01 inches) |
940 mm
(37.01 inches) |
1004 mm
(39.52 inches) |
940 mm
(37 inches) |
Weight | 209.1 kg
(460 lbs) fully loaded |
338.6 kg
(745 lbs) fully loaded |
512.3 kg
(1127 lbs) fully loaded |
717 kg
(1580 lbs) fully loaded |
691 kg
(1523 lbs) |
DC Input (per PSU) | 2x -48 to -60 V DC70 A to 55 A | 2x -48 to -60 V DC 70 A to 55 A | 2x -48 to -60 V DC 70 A to 55 A | 2x -48 to -60 V DC 70 A to 55 A | 2x -48 to -60 V DC 70 A to 55 A |
DC Branch Circuit Protection | 2x 90 A | 2x 90 A | 2x 90 A | 2x 90 A | 2x 90 A |
AC Input Voltage (per PSU) | 2x 200-240 V | 2x 200-240 V | 2x 200-240 V | 2x 200-240 V | 2x 200-240 V |
AC Branch Circuit Protection | 2x 20 A | 2x 20 A | 2x 20 A | 2x 20 A | 2x 20 A |
Input Power Circuits | 6 to 8 circuits(1) | 8 to 12 circuits(2) | 10 to 18 circuits(3) | 24 to 48 circuits(4) | |
Ambient Temperature | 0° to 40°C
(32° to 104°F) |
0° to 40°C
(32° to 104°F) |
0° to 40°C
(32° to 104°F) |
0° to 40°C
(32° to 104°F) |
|
Storage Temperature | -40° to 70°C
(-40° to 158°F) |
-40° to 70°C
(-40° to 158°F) |
-40° to 70°C
(-40° to 158°F) |
-40° to 70°C
(-40° to 158°F) |
|
Relative Humidity | 5 to 90% | 5 to 90% | 5 to 90% | 5 to 90% | |
Altitude | 0 to 3,000 meters
(0 to 10,000 feet) |
0 to 3,000 meters
(0 to 10,000 feet) |
0 to 3,000 meters
(0 to 10,000 feet) |
0 to 3,000 meters
(0 to 10,000 feet) |
|
Cooling | See Power draw configurations in Table 2 | See Power draw configurations in Table 2 | See Power draw configurations in Table 2 | See Power draw configurations in Table 2 |
1. For non-redundant power feeds, 12 to 16 for redundant power feeds.
2. For non-redundant power feeds, 16 to 24 for redundant power feeds.
3. For non-redundant power feeds, TBD for redundant power feeds.
4. For non-redundant power feeds, 24 to 48 for redundant power feeds.
The following table lists power specifications of modular switch components.
Module Type | Part Number | Power Draw (Typical / Maximum) |
---|---|---|
Supervisor Modules | DCS-7800-SUP
DCS-7800-SUP1A DCS-7800-SUP1S DCS-7816-SUP1A DCS-7816-SUP1S |
61 W / 72 W
61 W / 72 W 61 W / 72 W 71 W / 78 W 71 W / 78 W |
Linecard Modules | DCS-7800R3-48CQ
DCS-7800R3K-48CQ DCS-7800R3K-72Y DCS-7800R3-48CQM DCS-7800R3-48CQ2 DCS-7800R3-48CQM2 DCS-7800R3-48CQMS DCS-7800R3-36P DCS-7800R3A-36P DCS-7800R3A-36PM DCS-7800R3AK-36PM DCS-7800R3-36D DCS-7800R3A-36D DCS-7800R3A-36DM DCS-7800R3AK-36DM DCS-7800R3K-36DM DCS-7800R3A-36D2 DCS-7800R3A-36DM2 DCS-7800R3AK-36DM2 |
398 W / 462 W
398 W / 462 W 142 W / 178 W 620 W / 684 W 474 W / 622 W 511 W / 696 W 501 W / 666 W 825 W / 1136 W 533 W / 749 W 548 W / 764 W 578 W / 794 W 839 W / 1149 W 533 W / 749 W 548 W / 764 W 578 W / 794 W 1416 W / 1823 W 563 W / 779 W 578 W / 794 W 608 W / 824 W |
Fabric Modules | DCS-7804R3-FM
DCS-7808R3-FM DCS-7808R3-FM2 DCS-7812R3-FM DCS-7816R3-FM DCS-7816LR3-FM |
180 W / 248 W
510 W / 778 W 370 W / 518 W 681 W / 917 W 510 W / 778 W 510 W / 778 W |
Power Supply (AC) | PWR-D1-3041-AC-BLUE | 3 W / 10 W(1) |
Power Supply (DC) | PWR-D2-3041-DC-BLUE | 3 W / 10 W(1) |
7804 Series System | Full chassis loaded with:
2 - DCS-7800-SUP1A 6 - DCS-7804R3-FM 4 - DCS-7800R3-48CQ 6 - PWR-D1-3041-AC-BLUE |
3310 W / 4397 W |
7808 Series System | Full chassis loaded with:
2 - DCS-7800-SUP1A 6 - DCS-7808R3-FM 8 - DCS-7800R3-48CQ 8 - PWR-D1-3041-AC-BLUE |
6390 W / 8540 W |
7812 Series System | Full chassis loaded with:
2 - DCS-7816-SUP1A 6 - DCS-7812R3-FM 12 - DCS-7800R3-48CQ2 10 PWR-D1-3041-AC-BLUE |
12490 W / 14788 W |
7816 Series System | Full chassis loaded with:
2 - DCS-7816-SUP1A 12 - DCS-7816R3-FM 16 - DCS-7800R3-48CQ 24 - PWR-D1-3041-AC-BLUE |
12881 W / 17150 W |
7816L Series System | Full chassis loaded with:
2 - DCS-7816-SUP1A 6 - DCS-7816LR3-FM 16 - DCS-7800R3-48CQ 24 - PWR-D1-3041-AC-BLUE |
1 With no input power.
Note 1 Includes typical power supply conversion inefficiency. Contact your local Sales Engineer for 7800 power calculator details.
Note 2 Power numbers given as Typical/Maximum or Typical/Hot/Maximum where Hot is defined as 40°C Sea Level.
* Not N+N redundant power at worst case Temp/Elevation.